Inside The Condenser: From Latent Heat To Water Velocity

Seven tubes, 1.4 MW of condensing steam, an LMTD of 26.65 K, and 1.79 m/s of cooling water.

Nov 20, 20267 min read

Explorer · Tube bundle

5 °C in →→ 60 °C

Load per tube

200.4 kW

LMTD

26.65 K

Average h

19.15 kW/m²K

Water velocity

1.79 m/s

h here is an overall coefficient: condensing film, copper wall and water-side convection together. Equal load sharing across tubes is assumed.

Problem

Steam at Ts=68∘CT_s = 68^\circ\text{C} condenses on the outside of seven copper tubes, each with diameter D=0.025 mD = 0.025\ \text{m} and length L=5 mL = 5\ \text{m}. Cooling water enters at Ti=5∘CT_i = 5^\circ\text{C} and leaves at Te=60∘CT_e = 60^\circ\text{C}. Steam condenses at m˙cond=0.6 kg/s\dot m_\text{cond} = 0.6\ \text{kg/s}. Find the average heat-transfer coefficient hh and the mean water velocity VavgV_\text{avg} in each tube.

QuantityValue
Tubes NN7
D, LD,\ L0.025 m, 5 m
Ts, Ti, TeT_s,\ T_i,\ T_e68 °C, 5 °C, 60 °C
m˙cond\dot m_\text{cond}0.6 kg/s
hfgh_{fg} at 68 °C2338 kJ/kg
Water at 32.5 °C: cp, ρc_p,\ \rho4178 J/(kg·K), 994.8 kg/m³

Assume the load splits equally across identical tubes and the supplied properties are representative.

Heat Load

Condensing steam releases its latent heat:

Q˙total=m˙cond hfg=(0.6)(2338)=1402.8 kW,Q˙1=1402.87=200.4 kW per tube.\dot Q_\text{total} = \dot m_\text{cond}\,h_{fg} = (0.6)(2338) = 1402.8\ \text{kW}, \qquad \dot Q_1 = \frac{1402.8}{7} = 200.4\ \text{kW per tube}.

Log-Mean Temperature Difference

Steam stays at constant temperature, so the terminal differences are

ΔT1=68−5=63 K,ΔT2=68−60=8 K,\Delta T_1 = 68 - 5 = 63\ \text{K}, \qquad \Delta T_2 = 68 - 60 = 8\ \text{K}, ΔTlm=ΔT1−ΔT2ln⁡(ΔT1/ΔT2)=55ln⁡7.875≈26.65 K.\Delta T_\text{lm} = \frac{\Delta T_1 - \Delta T_2}{\ln(\Delta T_1/\Delta T_2)} = \frac{55}{\ln 7.875} \approx 26.65\ \text{K}.

The source writes the same value with both numerator and logarithm reversed; the positive form is used here so the sign convention is obvious.

Average Coefficient

As=πDL=π(0.025)(5)=0.3927 m2,A_s = \pi D L = \pi(0.025)(5) = 0.3927\ \text{m}^2, h=Q˙1As ΔTlm=200,400(0.3927)(26.65)≈19.15 kW/(m2K).h = \frac{\dot Q_1}{A_s\,\Delta T_\text{lm}} = \frac{200{,}400}{(0.3927)(26.65)} \approx 19.15\ \text{kW/(m}^2\text{K)}.

Water Flow And Velocity

m˙w=Q˙1cp(Te−Ti)=200,4004178(55)≈0.8721 kg/s per tube,\dot m_w = \frac{\dot Q_1}{c_p(T_e - T_i)} = \frac{200{,}400}{4178(55)} \approx 0.8721\ \text{kg/s per tube}, Vavg=4m˙wρπD2=4(0.8721)994.8 π(0.025)2≈1.79 m/s.V_\text{avg} = \frac{4\dot m_w}{\rho\pi D^2} = \frac{4(0.8721)}{994.8\,\pi(0.025)^2} \approx 1.79\ \text{m/s}.
ResultValue
hh≈ 19.15 kW/(m²·K)
VavgV_\text{avg} per tube≈ 1.79 m/s
Water flow, all seven tubes≈ 6.105 kg/s

Physical Interpretation

The chain runs from phase change to plumbing: latent heat sets the load, the load divides across tubes, LMTD sets the driving force, and the water energy balance plus continuity set the velocity. Note that hh here is an overall coefficient lumping condensation film, copper wall, and water-side convection — not the condensation coefficient alone.

Limitations

  • Equal load sharing ignores maldistribution in a real tube bundle.
  • Water properties are fixed at the mean bulk temperature.
  • Fouling and wall resistance are folded into hh rather than modelled separately.

Verification

CheckValue
Q˙1\dot Q_1200.4 kW
ΔTlm\Delta T_\text{lm}26.65 K
hh19.15 kW/(m²K)
m˙w\dot m_w, VavgV_\text{avg}0.8721 kg/s, 1.79 m/s

Source problem: Ch.8 Problem 8-29, condenser hh and cooling-water velocity.

Series · Heat Transfer Casebook

  1. Part 1

    Does A 700 W Copper Plate Pass ASME B31.3?

  2. Part 2

    The Thermal Window: Two Convection Systems, One Energy Balance

  3. Part 3

    Radiative Geometry: View Factors And A Black-Disk Balance

  4. Part 4

    Inside The Condenser: From Latent Heat To Water Velocity

All analysis

Comments (3)

Demo discussion
  • Dzvenislava Artyushenko

    Dzvenislava@blueswan305

    Good call noting that h lumps the film, wall, and water side together.

    • Ece Nalbantoğlu

      Ece@brownmeercat307

      Is 1.79 m/s comfortable for copper tubes, or close to erosion limits?

    • Mackenzie Anderson

      Mackenzie@smallzebra409

      I'd be curious how unequal tube loading would change the outlet temperatures.