Natural Convection

The Thermal Window: Two Convection Systems, One Energy Balance

Room-side buoyancy and a 20 mm air gap coupled at steady state to find a 3.9 °C outer pane — with an honest look at the correlation's range.

Nov 22, 20269 min read

Explorer · Coupled panes

Room 26 °CT₁ 18T₂ 3.9 °C20 mm gap

Ra_H

2.787e+9

h_o

2.859 W/m²K

Q̇ room = Q̇ gap

96.0 W

Outer pane T₂

3.9 °C

Heat rates balance at 96.0 W. Gap properties use a trial ΔT of 18.00 K (outer pane ≈ 0 °C); iterating with the solved ΔT gives 3.2 °C. H/L = 75 lies outside the correlation's 10–40 range.

Problem

A double-pane window is H=1.5 mH = 1.5\ \text{m} tall and W=2.8 mW = 2.8\ \text{m} wide with a vertical air gap of L=0.020 mL = 0.020\ \text{m}. The inner pane is at T1=18∘CT_1 = 18^\circ\text{C} and the room air is at T∞=26∘CT_\infty = 26^\circ\text{C}. Find (a) the heat-transfer rate from the room to the inner pane and (b) the outer-pane temperature T2T_2.

Two natural-convection systems are in series: buoyant room air falling along the cool inner pane, and air recirculating inside the narrow gap. Steady state couples them.

Given And Properties

QuantityValue
Window area As=HWA_s = HW4.2 m²
Room film temperature22 °C
Room air k, ν, Pr, βk,\ \nu,\ Pr,\ \beta0.02529 W/(m·K), 1.534×10⁻⁵ m²/s, 0.7304, 0.00339 K⁻¹
Gap air kg, νg, Prg, βgk_g,\ \nu_g,\ Pr_g,\ \beta_g0.02431 W/(m·K), 1.417×10⁻⁵ m²/s, 0.7339, 0.003546 K⁻¹
Gravity gg9.81 m/s²

Gap properties are evaluated at a trial outer-pane temperature T2≈0∘CT_2 \approx 0^\circ\text{C}, so the gap calculation starts from ΔTg≈18 K\Delta T_g \approx 18\ \text{K}.

Room-Side Convection

For a vertical plate the characteristic length is its height, and ΔT=8 K\Delta T = 8\ \text{K}:

RaH=gβ ΔT H3ν2Pr=9.81(0.00339)(8)(1.5)3(1.534×10−5)2(0.7304)≈2.787×109.Ra_H = \frac{g\beta\,\Delta T\,H^3}{\nu^2}Pr = \frac{9.81(0.00339)(8)(1.5)^3}{(1.534\times10^{-5})^2}(0.7304) \approx 2.787\times10^{9}.

The Churchill–Chu vertical-plate correlation gives

NuH={0.825+0.387 RaH1/6[1+(0.492/Pr)9/16]8/27}2≈169.5,Nu_H = \left\{0.825 + \frac{0.387\,Ra_H^{1/6}}{\left[1 + (0.492/Pr)^{9/16}\right]^{8/27}}\right\}^2 \approx 169.5, ho=NuH kH=169.5(0.02529)1.5=2.858 W/(m2K),h_o = \frac{Nu_H\,k}{H} = \frac{169.5(0.02529)}{1.5} = 2.858\ \text{W/(m}^2\text{K)}, Q˙room=hoAs(T∞−T1)=2.858(4.2)(8)=96.0 W.\dot Q_\text{room} = h_o A_s (T_\infty - T_1) = 2.858(4.2)(8) = 96.0\ \text{W}.

Gap Convection

RaL=gβg ΔTg L3νg2Prg=9.81(0.003546)(18)(0.020)3(1.417×10−5)2(0.7339)≈18,309.Ra_L = \frac{g\beta_g\,\Delta T_g\,L^3}{\nu_g^2}Pr_g = \frac{9.81(0.003546)(18)(0.020)^3}{(1.417\times10^{-5})^2}(0.7339) \approx 18{,}309.

For a vertical enclosure with H/L=75H/L = 75:

NuL=0.42 RaL1/4 Prg0.012(HL)−0.3≈1.333.Nu_L = 0.42\,Ra_L^{1/4}\,Pr_g^{0.012}\left(\frac{H}{L}\right)^{-0.3} \approx 1.333.

Correlation caveat. This correlation is stated for 10<H/L<4010 < H/L < 40. Here H/L=75H/L = 75, so the result is an extrapolation, not a validated value.

Coupled Energy Balance

At steady state the heat arriving at the inner pane must cross the gap:

Q˙room=Q˙gap=kg NuL AsL(T1−T2),\dot Q_\text{room} = \dot Q_\text{gap} = \frac{k_g\,Nu_L\,A_s}{L}(T_1 - T_2), 96.0=(0.02431)(1.333)(4.2)0.020(18−T2)=6.80(18−T2),96.0 = \frac{(0.02431)(1.333)(4.2)}{0.020}(18 - T_2) = 6.80(18 - T_2), T2=18−96.06.80≈3.9∘C.T_2 = 18 - \frac{96.0}{6.80} \approx 3.9^\circ\text{C}.
ResultValue
Room-to-window heat rate96.0 W
Outer-pane temperature≈ 3.9 °C

The outer pane is not the outdoor air temperature; it is an unknown solid surface found only by coupling the two heat rates.

A Consistency Note

The trial ΔTg=18 K\Delta T_g = 18\ \text{K} does not match the solved ΔTg=14.1 K\Delta T_g = 14.1\ \text{K}. Re-evaluating RaLRa_L with the solved difference (properties held fixed) and iterating converges to T2≈3.2∘CT_2 \approx 3.2^\circ\text{C}. The reference answer of 3.9 °C is kept here because it follows the stated procedure, but the explorer above shows both values so the single-pass assumption is visible rather than hidden.

Physical Interpretation

Warm room air sinks along the cooler inner pane in a thin buoyant boundary layer. Inside the gap, air rises against the warmer pane and falls against the colder one, forming a slow cell. With NuL≈1.3Nu_L \approx 1.3 that cell adds only about a third to pure conduction — which is exactly why narrow gaps insulate well.

Verification

CheckValue
AsA_s, LcL_c4.2 m², 1.5 m
RaHRa_H, NuHNu_H, hoh_o2.787×10⁹, 169.5, 2.858 W/(m²K)
RaLRa_L, NuLNu_L18,309, 1.333
T2T_23.9 °C
Q˙room−Q˙gap\dot Q_\text{room} - \dot Q_\text{gap} at T2T_20 W

Source problem: Ch.9 Problem 9-97, double-pane window air-gap temperature.

Series · Heat Transfer Casebook

  1. Part 1

    Does A 700 W Copper Plate Pass ASME B31.3?

  2. Part 2

    The Thermal Window: Two Convection Systems, One Energy Balance

  3. Part 3

    Radiative Geometry: View Factors And A Black-Disk Balance

  4. Part 4

    Inside The Condenser: From Latent Heat To Water Velocity

All analysis